Fire Detection System (PSM-A)
- Control Panel SOP (emitter has a dynamic acoustic signaling) to be installed in the control room design, degree of protection IP44;
-
Main unit SOP (only for PS-24-5A, SS-24-10A, PS-220/127-5A, PS-220/127-10A ) , is designed to connect a large number of sensors and connections to the control panel, the degree of protection IP20 .
-
Sensors (can be of two types: simple and combined) are designed for automatic detection and alarm of a possible fire.
-
Manual Call Points are designed to signal the fire of the corridors and rooms of the ship in which they are installed.
-
Remote control panel (for five-and ten-ray stations) IP56 , the system can be turned on a maximum of two panels ;
SOP letters 'Sch' (Switchboard version) designed for installation on the bulkhead.
If necessary, the system can be supplied with an uninterruptible power supply , which provides: basic nutrition SOP 220 VAC / 24 VDC supply ~ 220V, emergency power supply 24V SOP from the built in UPS batteries.
Properties:
- Ease of display (targeting) system allows you to define alarm and fault for each particular sensor indicating the control panel to its location;
- Equipment is manufactured in Russia and for Russia, that simplicity in terms of installation, operation, commissioning and maintenance. Specialists in the system are in the northern, southern and central parts of Russia;
- Each kit features an agreement with the register , and as each set is going for each customer his .
- Interchangeable cable equipment when changing from the old system, if the old cables have at least two cores and screen are not harmed by exclusion;
- Under each system developed project and agreed with the Register (RMRS or PPP);
- Operational technical support by phone or email.
Types of SOP 'PSM-A' | |||||||
Type |
Performance |
Radiation capacity SOP |
Mains voltage (basic) In |
Supply voltage.network (emergency) In |
Maxim. power consumption SOP DOS. / accident.(Without sensors), W |
||
Post. current |
AC. current |
Duty |
Mode |
||||
PS-24-2A -24-SS * 2ASCH |
Console |
2 |
24 |
- |
24 |
1.8 |
3 |
PS-220-2A -220-SS 2ASCH |
Console |
2 |
|
220 |
24 |
2,2 / 1,8 |
3.5 / 3 |
PS-24-5A -24-SS 5ASCH |
Console switchboards |
5 |
24 |
- |
24 |
5 |
6.5 |
PS-220/127-5A PS-220/127-5ASCH |
Console switchboards |
5 |
- |
220/127 * |
24 |
6/5 |
7.5 / 6.5 |
PS-10A-24 -24-SS 10ASCH |
Console |
10 |
24 |
- |
24 |
6.5 |
8 |
PS-220/127-10A PS-220/127-10ASCH |
Console switchboards |
10 |
- |
220/127 * |
24 |
7.5 / 6.5 |
9/8 |
* - PS-24 can be equipped with additional 2ASCH embedded power supply 220VAC / 24VDC.
Composition of sensors and detectors 'PSM-A' | ||||
Name sensor or instrument CCC 'PSM-A' |
Type of |
Degree of protection | Housing color | Power consumption, W (Dej. / ALARM.) |
Temperature sensor with a threshold address +65 ° C and audible alarm, the cabin | DT65ZS | IP20 | white | 0.2 / 0.25 |
Temperature sensor with a threshold address +65 ° C | DT65 | IP22 | white | 0.3 / 0.77 |
Temperature sensor waterproof address with a threshold of +65 ° C | DTV65 | IP55 | white | 0.2 / 0.25 |
Contact temperature sensor with a threshold of +65 ° C, the cabin | Preprint | IP20 | white | - |
Contact temperature sensor with a threshold of +65 ° C | SP | IP22 | white | - |
Waterproof temperature sensor pin with a threshold of +65 ° C, for machinery spaces | IPV | IP55 | white | - |
Waterproof temperature sensor pin with a threshold of +90 ° C, for machinery spaces | IPV90 | IP55 | white | - |
Temperature sensor with a threshold address +90 ° C | DT90 | IP22 | white | 0.2 / 0.25 |
Temperature sensor waterproof address with a threshold of +90 ° C, for machinery spaces | DTV90 | IP55 | white | 0.2 / 0.25 |
Detector combined with a threshold targeted 2-12% smoke and +65 ° C temperature, the cabin | PCM | IP20 | white | 0.3 / 0.65 |
Detector combined with a threshold targeted 2-12% smoke and +65 ° C temperature, for premises | IR | IP22 | white | 0.3 / 0.65 |
Detector combined with a threshold targeted 20-50% smoke and +65 ° C temperature, for machinery spaces | IK65 | IP44 | white | 0.3 / 0.65 |
Detector combined with a threshold targeted 20-50% smoke and +90 ° C temperature, for machinery spaces | IK90 | IP44 | white | 0.3 / 0.65 |
Detector manual address | TS | IP22 | red | 0.3 / 0.65 |
Handmade pin detector | IR-to | IP22 | red | - |
Detector manual targeted for dry areas | IRM | IP20 | red | 0.3 / 0.65 |
Handmade pin detector for dry areas | IRM-to | IP20 | red | - |
Waterproof handheld detector address, for machinery spaces and open decks | RWI | IP56 | red | 0.2 / 0.25 |
Waterproof handheld detector pin, for machinery spaces and open decks | RWI-to | IP56 | red | - |
Device interface with contact sensors address | CPM | IP56 | white | 0.8 / 0.25 |
Types of UPS | ||||||||
UPS type |
Performance | Mains voltage | Capacity AB, A * h |
Discharge current, A
occasionally discharge the battery before U ab = 22.2 |
||||
0.5 hr | 3h | 6h | 12h | 18h | ||||
IBP-220/24-7 2 |
Switchboard |
220 | 7.2 | 6.3 | 1.94 | 0.97 | 0.4 | 0.14 |
IBP-220/24-12 | Switchboard | 220 | 12 | 11.6 | 3.38 | 1.69 | 0.75 | 0.42 |
IBP-220/24-17 | Switchboard | 220 | 17 | 20.9 | 5.36 | 2.77 | 1.26 | 0.75 |
IBP-220/24-26 | Switchboard | 220 | 26 | 30.3 | 7.89 | 4.1 | 1.97 | 1.22 |
IBP-220/24-40 | Switchboard | 220 | 40 | 46 | 11.9 | 6.4 | 3.1 |
1.87 |
Navigation equipment RMRS (excerpt from the rules)
Compass magnetic core
Compass Magnetic Spare