ENG

BPS-114-24

BPS-114-24
Power Supply BPS-114-24 is designed for use as an uninterruptible power supply to consumers with a nominal input voltage of 24V DC and the total current consumption 12A. The primary network for BPS-114-24 should be used single-phase AC voltage 110/220 VAC, 50 Hz. 
 
Display and alarm system provided:
  • Two-color 4-segment LED display,
  • Audible alarm,
  • Relay alarm.
Operating position of the device - a vertical or floor. Not allowed BPS-114-24 installation in cabinets that do not provide ventilation, sufficient for its natural cooling hot parts, as well as at a distance of less than 1 m from heating systems.
 
BPS-114-24
 
Specifications: 
  • Supply voltage 110/220 V, 50/60 Hz 
  • Output voltage for mains operation 27,5 VDC 
  • Output voltage when running on battery 19.2. .24,8 VDC 
  • Maximum output current for mains operation 12 A 
  • Maximum life from the battery when a load of 10 A at least 60 minutes 
  • Tripping current 20 A 
  • Efficiency 72% 
  • Power 320 W 
  • Battery built, helium, not serviced, 2pcs 12V 16Ach size (181h76h167) 
  • Dimensions 410 x 295 x 205 mm 
  • Protection class IP 22 
  • Storage temperature -20. . +60 ° C 
  • Operating temperature -10. . +50 ° C 
  • Weight not exceeding 16 kg
Input voltage
220 VAC
Output voltage
24 VDC
Available for order

BPS-114-24

to order
Call our sales manager