TCD 563 - is a heat detector designed to detect fire and severe smoke. It is used in fire alarm systems SecuriFire 3000, SecuriPro and SFP 512. The principle of operation is to determine the temperature range, the gradient of which is specified in the standard EN 54-5. The alarm is accompanied by a light signaling LED indicator. Meets the requirements of CEN-EN 54 and CE.
 
Types of fire alarm signals generated by the thermal detector TCD 563:
  • Thermal signal.
  • Thermal signal in test mode
  • Signal thermal alarm signal
The detector also reports on a fault that has occurred, for example, when the sensor is shorted, the power supply error, the EERPOM memory error. To reduce false alarms, the sensor is equipped with a specialized filter. It is recommended to turn off this filter during service. The TCD 563 is equipped with a digital signal processing function. Has a multi-dimensional event memory.
 
It should be noted that the device must not be placed in rooms with production of heat, steam and dust. The TCD 563 is mounted using a universal USB 501 socket. The device is electrically connected via terminals and a 5-pin connector.
 
Specifications:
  • Operating voltage - 18 - 30 VDC
  • Connection - SecuriLine via MDI 82
  • Protection class with USB socket 501- IP 44
  • Operating temperature - -25 + 70С
  • Relative humidity - 95%
  • Weight - 125 gr